1100 kV特高压气体绝缘开关套管-支架体系抗震性能加固试验研究Tests on Seismic Retrofitting of 1100 kV UHV GIS Bushing-Supporting Frame System
何畅;谢强;杨振宇;
摘要(Abstract):
气体绝缘开关(gas insulated switchgear,GIS)套管是特高压(ultra-high voltage,UHV)变电站中的重要设备。为提高某型1100 kV特高压GIS套管-支架体系的抗震性能,对该套管原有钢支架梁柱节点进行了加固,并增加了相应斜撑,对加固前后的套管-支架体系进行了振动台试验。结果表明:加固前原支架在不同地震作用下动力特性发生变化,抗震性能不满足相关规范要求。支架对套管地震响应有较大的放大作用,加固后的支架侧向刚度增强,支架顶部加速度反应谱峰值较加固前降低,且主要频率分量升高,与套管基频差异增加,套管-支架体系地震响应较加固前减小。支架对体系抗震性能有较大影响,加固后的支架能显著提高GIS套管-支架体系的抗震性能。
关键词(KeyWords): 特高压气体绝缘开关;套管支架;地震响应;振动台试验;抗震加固
基金项目(Foundation): 国家电网公司科技项目(SGTYHR/14-JS-188);; 教育部霍英东教育基金会优选资助课题(114021)~~
作者(Author): 何畅;谢强;杨振宇;
Email:
DOI: 10.13335/j.1000-3673.pst.2017.2227
参考文献(References):
- [1]干喆渊,赵军,张建功,等.GIS隔离开关操作过程中管壳空间暂态电磁辐射计算[J].高电压技术,2016,42(3):980-986.Gan Zheyuan,Zhao Jun,Zhang Jiangong,et al.Computation of transient electromagnetic field emission from enclosure during GIS disconnector switching operations[J].High Voltage Engineering,2016,42(3):980-986(in Chinese).
- [2]Zareei S A,Hosseini M,Ghafory-Ashtiany M.The role of equipment in seismic risk of power substations[J].Proceedings of the Institution of Civil Engineers,2017,170(4):1-13.
- [3]Moustafa M A,Mosalam K M.Structural performance of porcelain and polymer post insulators in high voltage electrical switches[J].Journal of Performance of Constructed Facilities,2016,30(5):4016002.
- [4]三嶋隆樹,横村忠幸,高橋明男.新潟県中越沖地震における所内変圧器火災の状況および課題解決に向けた取り組み[J].火災,2008,58(2):5-10.Takaki M,Tadayuki Y,Akio T.Lessons learned from the transformer fire in the Niigata-ken Chuetsu-oki Earthquake and actions for solving the problems[J].Fire Disaster,2008,58(2):5-10(in Japanese).
- [5]Fujisaki E,Takhirov S,Xie Q,et al.Seismic vulnerability of power supply:Lessons learned from recent earthquakes and future horizons of research[C]//Proceedings,9th International Conference on Structural Dynamics,EURODYN,Porto,Portugual,2014:345-350.
- [6]Johnson F,Iliev K.Earthquake effects on SDG&E's 500/230 kV Imperial Valley Substation[C]//2012 IEEE Power and Energy Society General Meeting,San Diego,USA:IEEE,2012:4310-4312.
- [7]Goodno B J,Gould N C,Caldwell P,et al.Effects of the January 2010Haitian earthquake on selected electrical equipment[J].Earthquake Spectra,2011,27(Supplement 1):S251-S276.
- [8]Eidinger J,Davis C,Tang A,et al.9.0 M Tohoku earthquake,March11,2011,performance of water and power systems[R].[S.1.]:G&E Engineering Systems Inc.2012.
- [9]刘如山,刘金龙,颜冬启,等.芦山7.0级地震电力设施震害调查分析[J].自然灾害学报,2013,22(5):83-90.Liu Rushan,Liu Jinlong,Yan Dongqi,et al.Seismic damage investigation and analysis of electric power system in Lushan M 7.0earthquake[J].Journal of Natural Disasters,2013,22(5):83-90(in Chinese).
- [10]刘振林,卢智成,张搏宇,等.特高压瓷套避雷器标准化抗震性能优化[J].电网技术,2016,40(5):1570-1575.Liu Zhenlin,Lu Zhicheng,Zhang Boyu,et al.Optimization research on seismic safety performance of UHV porcelain bushing lightning arrester standardization[J].Power System Technology,2016,40(5):1570-1575(in Chinese).
- [11]谢强,何畅,杨振宇,等.±800 kV特高压直流穿墙套管地震模拟振动台试验研究[J].电网技术,2018,42(1):140-146.Xie Qiang,He Chang,Yang Zhenyu,el al.Shaking table tests on±800kV UHV DC wall bushing[J].Power System Technology,2018,42(1):140-146(in Chinese).
- [12]程永峰,王海菠,卢智成,等.特高压电抗器-套管体系抗震性能及本体动力放大作用计算方法研究[J].中国电机工程学报,2017,37(20):6109-6117.Cheng Yongfeng,Wang Haibo,Lu Zhicheng,et al.Seismic performance and calculation method of dynamic amplification of body research of UHV reactor-bushing system[J].Proceedings of the CSEE,2017,37(20):6109-6117(in Chinese).
- [13]程永锋,朱祝兵,卢智成,等.硬管母联接的500 kV避雷器和互感器耦联体系地震模拟振动台试验研究[J].电网技术,2016,40(12):3945-3950.Cheng Yongfeng,Zhu Zhubing,Lu Zhicheng,et al.Earthquake simulation shaking table test on coupling system of 500 kV surge arrester and instrument transformer interconnected with rigid tube bus[J].Power System Technology,2016,40(12):3945-3950(in Chinese).
- [14]何畅,谢强,杨振宇,等.特高压直流穿墙套管-阀厅体系地震响应及抗震性能提升措施[J].高电压技术,2017,43(10):3215-3223.He Chang,Xie Qiang,Yang Zhenyu,et al.Seismic responses and retrofitting countermeasures for UHVDC wall bushing-valve hall system[J].High Voltage Engineering,2017,43(10):3215-3223(in Chinese).
- [15]Mohammadi R K,Akrami V,Nikfar F.Dynamic properties of substation support structures[J].Journal of Constructional Steel Research,2012(78):173-182.
- [16]中华人民共和国建设部.GB 50017—2003钢结构设计规范[S].北京:中国计划出版社,2003.
- [17]国家电网公司.Q/GDW11132—2013特高压瓷绝缘电气设备抗震设计及减震安装与维护技术规程[S].北京:中国电力出版社,2014.
- [18]中华人民共和国住房和城乡建设部.GB 50260—2013电力设施抗震设计规范[S].北京:中国电力出版,2013.
- [19]IEEE Power Engineering Society.IEEE Std 693—2005 IEEE recommended practice for seismic design of substations[S].New York:2005.
- [20]Mohammadi R K,Nikfar F,Akrami V.Estimation of required slack for conductors connecting substation equipment subjected to earthquake[J].IEEE Transactions on Power Delivery,2012,27(2):709-717.
- [21]Kimura H.Examination system for accelerator with parallel link mechanism displacement calculation by integrated acceleration and individual correction of accelerators[J].Transactions of the Japan Society of Mechanical Engineers,2012,78(785):27-34.